Schneider Electrics Innovation Summits are all about preparing you to lead in this era.Create an integer variable called CleanTimer and a new Panel under the Base Panels.
![]() ![]() The next operation is to create a Panel operation to Change Panel and the Panel ID will be the ID of the Panel you just created. Go to the Label, create a static label Push this button to disable touch input for 20 secs so HMI panel can be cleaned. Now, go into the new panel you created and create a Numeric field object. The first action will we set as follows: Set trigger type to Periodic with a frequency (secs) of 1, and scheduling at Low. Now, create a Word operation, set the Source to 1, Operation will be subtract, and Destination is CleanTimer. Once the operation settings is complete, click Add button and then Finish. Create a second action as a Conditional Trigger Type, set the Trigger Variable to CleanTimer and Condition to When False. Now, create a Panel operation and set it to change to the Previous Panel. Vijeo Designer 6.2.5 Download The ProjectSee below for illustration Please compile the project and either download the project to the HMI or simulator. Also, attached is a sample Vijeo Designer v4.6C project for the clean screen. It will describe the email program and what to expect in the upcoming weeks.